soneil



Joined: 21 Jul 2008
Posts: 3

PostPosted: Mon Jul 21, 2008 9:21 am    Post subject: SentryII Com port problem Reply with quote

I have a Pro1500e and am running SentryII 2.00.03 on Windows Server 2003. I have installed the USB serial driver and rebooted. Device Manager and SentryII both see the new Com port, Com3. When I run SentryII and configure the port, it says settings are saved, but it keeps reverting to Com1. I can't find a line to configure the port in the SentryII.ini file to manually configure the port. Any help would be appreciated.
Back to top
View user's profile Send private message
jeff



Joined: 19 Jan 2006
Posts: 187

PostPosted: Mon Jul 21, 2008 1:58 pm    Post subject: SentryII Reply with quote

soneil,

I have seen that myself.

What I do is:

I shut the web browser off and restart the web browser.
Back to top
View user's profile Send private message
soneil



Joined: 21 Jul 2008
Posts: 3

PostPosted: Tue Jul 22, 2008 1:53 pm    Post subject: SentryII Reply with quote

Closing and reopening the web browser did not help.
Back to top
View user's profile Send private message
jeff



Joined: 19 Jan 2006
Posts: 187

PostPosted: Tue Jul 22, 2008 2:53 pm    Post subject: SentryII Reply with quote

soneil,

Stop the service first, then open the Sentry II folder in your explorer. Look for Minuteman open Sentryini.

Do you have Windows XP?



Jeff
Back to top
View user's profile Send private message
tvancil
Site Admin


Joined: 30 Mar 2000
Posts: 231
Location: Carrollton, TX 75007

PostPosted: Wed Jul 23, 2008 10:28 am    Post subject: Reply with quote

soneil-

Try the following:

1) Stop the SentryII service and open the SentryII.ini file located here (in Notepad or text editor):
C:\Program Files\Minuteman\SentryII\SentryII.ini

2) Be sure the contents of the file look something like the ones pasted at the bottom of this post. If not, then copy and paste the text between the # lines into your SentryII.ini file.

3) Find this section in the file and manually change the port to COM3.
[Comms]
UPSPollInterval=1000
Port=COM1

4) Save the file and close it.

5) Restart the SentryII service and try to open the SentryII page in your browser again.

If manually changing the ini file doesn't fix the problem, then try the following:
1) Uninstall SentryII 2.00.03

2) Download and install version 2.01.03
http://www.minutemanups.com/support/software/sentryII-v2-01-03-win32.zip

Version 2.01.03 fixed an issue with SentryII and the PRO-E USB virtual COM driver that sometimes happens in XP. Usually the drop-down would show three COM3 entries instead of what you described. However, it's possible that Server 2003 is experiencing the same or similar problem but presents itself differently.

Please try and let us know what happens.

Todd

############Typical SentryII.ini file#############
[DCL]
Parasys Read Extra Bytes=1
Device_DLL_0=C:\Program Files\Minuteman\SentryII\ParaSysUPSDLL.dll
Device_DLL_1=C:\Program Files\Minuteman\SentryII\MegaTechUPSDLL.dll
AppPath=C:\Program Files\Minuteman\SentryII\nomvltgs.ini
LastReadByteCount=72
Nominal Battery Voltage=12
[Web Server]
Port=80
[DefaultUser]
Preference0=Manufacturer
Preference1=Model
Preference2=Output Source
Preference3=Battery Status
Preference4=Input Voltage
Preference5=Battery Voltage
Preference6=Output Voltage
Preference7=Input Voltage
Preference8=Output Voltage
Preference9=Battery Voltage
[Comms]
UPSPollInterval=1000
Port=COM1
[Server]
Event Log Path=C:\Program Files\Minuteman\SentryII\EventLog
Data Log Path=C:\Program Files\Minuteman\SentryII\DataLog
Log Name Prefix=MIN_P
SMTP Address=
[admin]
Preference0=Manufacturer
Preference1=Model
Preference2=Output Source
Preference3=Battery Status
Preference4=Input Voltage
Preference5=Battery Voltage
Preference6=Output Voltage
Preference7=Input Voltage
Preference8=Output Voltage
[Input Bad]
Shutdown_OS_Delay=500
Shutdown_OS_Message=
Shutdown_Enabled=true
Shutdown_UPS_Delay=600
SystemCommand_CommandPathAdd=
SystemCommand_OptionalCommandParamsAdd=
SystemCommand_OptionalCommandParamsRemove=
SystemCommand_CommandPathRemove=
SystemCommand_Delay=10
SystemCommand_Enabled=true
[API]
Port=8888
[SIIRemote]
LINK_KEY_0=localhost
[Schedule]
MaxSchedule=0
##################################
Back to top
View user's profile Send private message Send e-mail Visit poster's website
soneil



Joined: 21 Jul 2008
Posts: 3

PostPosted: Mon Jul 28, 2008 10:01 am    Post subject: SentryII Reply with quote

Thank you for your responses. Manually adding the line Port=COM3 to the [Comms] section did the trick. In addition I have downloaded the newer version of SentryII and will install it during our next scheduled upgrade cycle.
Back to top
View user's profile Send private message
tvancil
Site Admin


Joined: 30 Mar 2000
Posts: 231
Location: Carrollton, TX 75007

PostPosted: Mon Jul 28, 2008 10:32 am    Post subject: Reply with quote

Thanks for responding back to let us know what happened. We're glad to hear that it is up and running now.
Back to top
View user's profile Send private message Send e-mail Visit poster's website
Display posts from previous:   
Post new topic   Reply to topic    MinutemanUPS.com Forum Index -> Software All times are GMT - 6 Hours
Page 1 of 1

 
Jump to:  
You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot vote in polls in this forum


Powered by phpBB © 2001, 2005 phpBB Group